Product Overview
Category: Fire PumpsXBD-SYW Horizontal Fire Pump. Engineered for fire protection water supply and pressure boosting systems. Contact Shenyin Pump for duty-point review, materials and configuration options.
- Duty-point review and pump selection support
- Outline drawings and installation instructions available
Export inquiry support
Need help selecting XBD-SYW Horizontal Fire Pump?
Send flow, head, medium, temperature, voltage/frequency, quantity and destination country. Our engineering team can review duty point, materials, seal type and configuration for OEM, EPC and export projects.
Technical Information
The information below is for reference. Final order data is subject to the technical agreement and product nameplate.
I. Product Overview
The XBD-SYW series horizontal single-stage single-suction fire-fighting pump unit is designed to transport clear water (free of solid particles) and liquids with physical and chemical properties similar to water. It is primarily used for pipeline pressurization and water delivery in fire-fighting systems. Additionally, it is widely applicable in industrial and municipal water supply and drainage, high-rise building water pressurization, long-distance water transport, HVAC circulation, boiler feed water, cooling circulation, and equipment integration.
The XBD-SYW horizontal fire-fighting pump features a horizontal end-suction centrifugal pump structure, characterized by stable operation, low vibration, high efficiency, and ease of maintenance. With a rational structural design and convenient installation and maintenance, it meets the requirements for long-term, stable operation in various fire-fighting water supply systems.
The performance and technical specifications of the XBD-SYW fire-fighting pump unit manufactured by our company comply with the latest national standard GB6245-2006 "Fire-fighting Pumps," as well as the mandatory product certification implementation rules (CNCA-C18-03:2014) and implementation details (CCCF-MHSB-08). The product has passed testing by the National Fire-fighting Equipment Quality Supervision and Inspection Center and has obtained the China Compulsory Certification (CCC) for fire-fighting products.
We utilize advanced CAD hydraulic modeling and computer optimization technologies, supported by comprehensive machining and testing equipment and a rigorous quality management system, ensuring stable performance, reliable operation, and excellent quality.
II. Product Features
1. Features a horizontal single-stage single-suction structure that is simple, rational, and ensures stable operation as well as convenient installation and maintenance.
2. Employs a coaxial direct-connection structure between the pump and motor, ensuring high concentricity, low vibration, low noise, and smooth operation.
3. Utilizes advanced hydraulic model design for high operating efficiency, helping to reduce energy consumption while offering a wide performance range.
4. Uses a high-quality mechanical seal for the shaft, offering advantages such as wear resistance, zero leakage under normal conditions, and a long service life.
5. The pump casing is precision-cast from high-quality cast iron, providing high structural strength and strong pressure-bearing capacity.
6. Inlet and outlet flanges comply with national standards, facilitating on-site pipeline installation and system integration.
7. Easy maintenance: components such as the impeller and mechanical seal can be serviced without dismantling the piping. 8. Suitable for long-term standby and emergency start-up fire-fighting applications; offers high reliability.
III. Technical Parameters
Flow rate: 5–200 L/s;
Pressure: 0.10–2.0 MPa;
Power: 1.5–315 kW;
Rotational speed: 980–2950 r/min;
Inlet/Outlet diameter: φ50–φ300;
Medium temperature: ≤80°C;
Working pressure: ≤2.5 MPa.
IV. Main Applications
1. Fire water supply systems for high-rise buildings;
2. Fire hydrant systems;
3. Automatic sprinkler fire extinguishing systems;
4. Industrial and civil fire water supply;
5. Municipal fire water supply systems;
6. Fire protection systems for warehousing and logistics;
7. Fire-fighting pressure-boosting water supply for industrial and mining enterprises;
8. Fire-fighting pressure-stabilizing and circulating water supply systems.
V. Installation and Operating Conditions
1. The pumped medium should be clean water or a liquid with physical and chemical properties similar to clean water;
2. The medium must be free of solid particles and long fibers;
3. Ambient temperature not exceeding 40°C;
4. Relative humidity not exceeding 95%;
5. Power supply frequency: 50 Hz; voltage: 380 V (special voltages available upon request);
Model Designation
XBD 8.0/30G-SYW
Shenyin horizontal single-stage single-suction fire pump
Rated flow rate (30L/s)
Rated pressure (0.8MPa)
Motor-driven fire pump unit